HOME >Product information>Cooling tower products>counter type (DHG-CU) |
 |
|
| |
 |
| |
|
Model
/ Item |
Capacity |
Fan
assembly |
Piping
diameter |
PDF down |
Cooling
capacity
(RT)
|
Heatload
(Kcal/hr)
|
Circulating
water flow
rate (§©/hr)
|
Motor |
Hot
water
inlet A(B) |
Cold
water
outlet A(B) |
Spec |
DWG |
Rated
output/Cell(HP) |
DHG-CU-150 |
150 |
585,000 |
117 |
5 |
150(1) |
150(1) |
 |
 |
DHG-CU-175 |
175 |
682,500 |
136.5 |
7.5 |
150(1) |
150(1) |
 |
 |
DHG-CU-200 |
200 |
780,000 |
156 |
7.5 |
150(1) |
150(1) |
 |
 |
DHG-CU-225 |
225 |
877,500 |
175.5 |
7.5 |
200(1) |
150(1) |
 |
 |
DHG-CU-250 |
250 |
975,000 |
195 |
10 |
200(1) |
200(1) |
 |
 |
DHG-CU-300 |
300 |
1,170,000 |
234 |
10 |
200(1) |
200(1) |
 |
 |
DHG-CU-350 |
350 |
1,365,000 |
273 |
15 |
200(1) |
200(1) |
 |
 |
DHG-CU-400 |
400 |
1,560,000 |
312 |
20 |
250(1) |
250(1) |
 |
 |
DHG-CU-500 |
500 |
1,950,000 |
390 |
20 |
250(1) |
250(1) |
 |
 |
DHG-CU-600 |
600 |
2,340,000 |
468 |
25 |
250(1) |
250(1) |
 |
 |
DHG-CU-800 |
800 |
3,120,000 |
624 |
20 |
250(2) |
250(2) |
 |
 |
DHG-CU-1000 |
1,000 |
3,900,000 |
780 |
20 |
250(2) |
250(2) |
 |
 |
|
|
|
|
|
|
| |
|
| |
|
|
|
|
|